1. Uvod
This manual provides detailed instructions for the installation, operation, maintenance, and troubleshooting of the MARSTEK Triple Power 63A 110/120V Automatic Transfer Switch (ATS). This device is designed to automatically switch between three power sources (e.g., utility power, generator, inverter) to ensure a continuous and stable power supply to connected loads. It incorporates advanced protection features against overvoltage, undervoltage, and overcurrent conditions.
Please read this manual thoroughly before installation and operation to ensure safe and efficient use of the product.
2. Sigurnosne informacije
WARNING: Risk of Electric Shock. Installation and servicing should only be performed by qualified personnel.
- Always disconnect all power sources before installing or servicing the ATS.
- Osigurajte ispravno uzemljenje uređaja.
- Verify all wiring connections are secure and correct according to the wiring diagram.
- Do not operate the ATS if it appears damaged.
- Pridržavajte se svih lokalnih i nacionalnih električnih propisa.
- This device is not suitable for use with neutral-bonded generators without appropriate isolation or modification to prevent ground fault issues. Consult a qualified electrician if using with such generators.

Image: Safety warning indicating to power off and test for electricity before installation. Always ensure zero voltage is detected before proceeding with any work on the device.
3. Značajke proizvoda
The MARSTEK Triple Power 63A ATS offers a range of features designed for reliable power management:
- Triple-Source Automatic Switching: Seamlessly transfers loads between Primary, Backup 1, and Backup 2 power sources during outages, voltage sags/surges, or irregularities. Automatically reverts to the preferred source once stable.
- Built-in Electrical Protection: Safeguards connected equipment with advanced Overvoltage (140V max), Undervoltage (90V min), and Overcurrent (63A max) protection, preventing damage from unstable power.
- Flexible Priority Phase Setting: Designate ANY input (L1/L2/L3) as Primary—optimize for cost, reliability, or grid conditions without fixed "Main" limitations.
- Real-Time LED Voltage Monitoring: Intuitive display shows live voltage levels (e.g., 120V, 108V) for all 3 sources, with instant status indicators for active source, transfer, and faults.
- Quick DIN Rail Installation & Compact Design: Space-saving unit installs in minutes via standard DIN rail mounting, rated for 63A at AC 110V with a 106 mechanical lifespan.

Image: Visual representation of the intelligent protection features, including overvoltage, undervoltage, and overcurrent protection, designed to safeguard connected equipment.

Image: Detailed breakdown of the comprehensive electrical protection, showing default and adjustable values for overvoltage (>140V), undervoltage (<90V), and overcurrent (>63A).

Image: Diagram demonstrating the flexibility to set any input phase (L1, L2, or L3) as the primary power source, optimizing power configuration based on reliability or cost.
4. Sadržaj paketa
Paket proizvoda uključuje:
- 1 x MARSTEK Triple Power 63A 110/120V Automatic Transfer Switch
Note: DIN rail may be included separately or integrated. Please check your packaging.
5. Specifikacije
| Parametar | Vrijednost |
|---|---|
| Rated Supply Voltage | AC 110V (N-L1/L2/L3) |
| Nazivna radna struja | 63 Amps |
| Operating Voltage | 120 Volts |
| Transfer Speed | 1-600s (Adjustable, 5s Default) |
| Mehanički život | 106 operacije |
| Overvoltage Zaštita | Adjustable 120V-300V (Default 140V) |
| Undervoltage Zaštita | Adjustable 80V-210V (Default 90V) |
| Overcurrent Protection | Adjustable 1A-63A (Default 63A) |
| Način rada | UKLJUČENO ISKLJUČENO |
| Vrsta kontakta | Normalno zatvoreno |
| Tip konektora | Priključak |
| Terminal | Screw |
| Tip kruga | 3-way |
| Kontakt materijal | Bakar |
| Dimenzije proizvoda (D x Š x V) | 4.3 x 3.5 x 3.3 inča |
| Težina | 15.2 unce |

Image: Diagram illustrating the physical dimensions of the ATS and a summary table of its key electrical and mechanical specifications.
6. Instalacija
6.1 Montaža na DIN šinu
The MARSTEK ATS is designed for quick and easy installation on a standard DIN rail.
- Ensure all power sources are disconnected and verified as de-energized.
- Align the back panel display of the ATS with the DIN rail.
- Press the latch located on the bottom of the ATS.
- Insert the ATS onto the DIN rail.
- Release the latch to secure the ATS firmly in place. You should hear a "click" sound.

Image: Step-by-step visual guide for installing the ATS onto a DIN rail, demonstrating the alignment, latch pressing, insertion, and latch release process.
6.2 Dijagram ožičenja
Refer to the following diagram for correct wiring connections. Ensure all connections are tight and properly insulated.

Image: Detailed wiring diagram illustrating the input connections for Neutral (N), Line 1 (L1), Line 2 (L2), Line 3 (L3), and output connections for Neutral (N) and Line (L).
- Ulazni priključci: Connect your three power sources (e.g., Utility, Generator, Inverter) to L1, L2, and L3 respectively. Connect the neutral lines to the N terminals.
- Izlazni priključci: Connect your load to the N (Neutral) and L (Line) output terminals.
- Važno: Ensure correct phase and neutral connections. Incorrect wiring can damage the device or connected equipment.
7. Operacija
7.1 Power-On and Initial State
Once wired and power is applied, the ATS will perform a self-check. The LED display will show the voltage levels of the connected sources. The device will automatically select the primary source (as configured) if it is stable and within acceptable parameters.

Image: Close-up of the multi-function digital adjustment panel, featuring a high-definition LED display for real-time voltage and current monitoring, alongside menu options for customizing parameters.
7.2 Automatic Switching Logic
The ATS continuously monitors the voltage and stability of all three connected power sources. The switching logic is as follows:
- If the designated primary source (L1, L2, or L3) is stable and within acceptable voltage/current limits, the load will be connected to it.
- If the primary source experiences an outage, voltage sag/surge, or overcurrent condition, the ATS will automatically transfer the load to the next available stable backup source (Backup 1, then Backup 2).
- Once the primary source is restored and stabilized, the ATS will automatically revert the load back to the primary source after a configurable delay.

Image: Flowchart depicting the automatic switching mechanism, showing how the ATS transitions between the normal power source and backup sources in response to power outages ili voltage abnormalities, and reverts once stability is restored.
7.3 Podešavanje parametara
The ATS features a digital adjustment panel for customizing various parameters. Use the 'M' (Menu), 'Up' (Digit+), and 'Down' (Digit-) buttons to navigate and adjust settings.
- Power-on delay time (PE): Time delay before the ATS powers on after initial power application.
- Transfer time/Protection recovery delay time (rE): Delay before switching to a backup source or reverting to primary.
- Overvoltage protection value (oU): Sets the upper voltage limit.
- Undervoltage protection value (UU): Sets the lower voltage limit.
- Priority phase (PS): Designate L1, L2, or L3 as the primary power source.
- Overcurrent protection value (oC): Sets the maximum current limit.
- Overcurrent protection action time (CtT): Delay before overcurrent protection trips.
- Continuous overcurrent protection frequency (CC): How often overcurrent protection can trip.
Refer to the on-screen menu for specific navigation and adjustment procedures. Always ensure settings are appropriate for your electrical system and connected loads.
8. Održavanje
The MARSTEK ATS is designed for minimal maintenance. However, regular checks can ensure optimal performance and longevity:
- Vizuelni pregled: Povremeno provjeravajte uređaj na bilo kakve znakove fizičkog oštećenja, labavih spojeva ili promjene boje.
- Provjere veze: Ensure all wiring terminals remain tight. Loose connections can lead to overheating and device failure.
- čistoća: Uređaj držite čistim od prašine i ostataka. Za čišćenje koristite suhu, meku krpu. Ne koristite tekuća sredstva za čišćenje.
- Test funkcionalnosti: If possible and safe to do so, periodically test the automatic transfer function by simulating a power outage on the primary source.
WARNING: Always disconnect power before performing any maintenance or cleaning.
9. Otkrivanje problema
| Problem | Mogući uzrok | Rješenje |
|---|---|---|
| Uređaj se ne uključuje. | Nema ulaznog napajanja; nepravilno ožičenje; unutrašnji kvar. | Verify input power to L1/L2/L3 and N terminals. Check wiring against diagram. If power is present and wiring is correct, contact support. |
| Nema automatskog transfera. | Backup source not stable; primary source still active; incorrect settings (e.g., transfer delay). | Provjerite voltage of backup sources. Ensure primary source is truly unavailable. Review transfer delay settings (rE). |
| Frequent tripping (Overvoltage/Undervoltage/Overcurrent). | Unstable power supply; load exceeds rating; protection settings too sensitive. | Monitor power quality. Reduce load if exceeding 63A. Adjust protection thresholds (oU, UU, oC) if appropriate for your system, but do not exceed safe limits. |
| GFI/GFCI trips when using a generator. | Generator has a neutral-ground bond, creating multiple bonding points when connected to a house system. | This ATS is designed for systems where neutral and ground are bonded at a single point (e.g., main service panel). If using a neutral-bonded portable generator, consult a qualified electrician for proper isolation or alternative wiring solutions to avoid ground fault issues. |
| LED display shows "Fault". | Indicates an error condition (e.g., overvoltage, undervoltage, overcurrent). | Check the specific fault indicator (L1, L2, L3, Fault LED). Address the underlying power issue or load condition. Review protection settings. |
10. Garancija i podrška
MARSTEK products are manufactured to high-quality standards. For warranty information, please refer to the terms and conditions provided at the point of purchase or contact MARSTEK customer support.
If you encounter any issues not covered in this manual or require further assistance, please contact MARSTEK customer service through your retailer or the official MARSTEK website.