1. Uvod
This manual provides detailed instructions for the installation, operation, and maintenance of your OJ Microline UTN4-4999 (Model UDG-4999) Non-Programmable Thermostat. This thermostat is designed for electric radiant floor heating systems and features dual sensing (air and floor) and dual voltage capabilities (120V & 240V). It includes a built-in Class A GFCI for enhanced safety.
The OJ Microline UTN4-4999 offers straightforward temperature control without complex programming, making it ideal for users seeking a simple and effective solution for their floor heating needs.

Slika 1: Prednja strana view of the OJ Microline UTN4-4999 Non-Programmable Thermostat, displaying time and temperature.
2. Sigurnosne informacije
Važna sigurnosna uputstva:
- Električna opasnost: Installation must be performed by a qualified electrician in accordance with local and national electrical codes. Disconnect power at the circuit breaker before installation or servicing.
- Prekidač uzemljenja (GFCI): This thermostat includes a built-in Class A GFCI, which is required for all underfloor heating systems. Test the GFCI regularly as per local codes and manufacturer recommendations.
- Voltage Kompatibilnost: Osigurajte da je volumen termostatatage (120V or 240V) matches your heating system's voltage.
- Podni senzor: The included floor sensor must be properly installed to prevent overheating and ensure accurate temperature control.
- Nemojte uranjati the thermostat or sensor in water.
- Ne raditi the thermostat with damaged wiring or if it has been dropped or damaged.

Figure 2: The OJ Microline thermostat installed in a bathroom, highlighting its sleek design and integration.
3. Podešavanje i instalacija
Installation of the OJ Microline UTN4-4999 thermostat requires adherence to electrical safety standards. It is recommended that a qualified electrician performs the installation.
3.1 Kontrolna lista pred instalaciju
- Verify that the power supply to the heating system is disconnected at the main circuit breaker.
- Potvrdite voltage of your heating system (120V or 240V) matches the thermostat's capabilities.
- Ensure you have all necessary tools: screwdriver, wire strippers, electrical tape, etc.
- Locate a suitable wall box for mounting the thermostat.
3.2 Dijagram ožičenja
Refer to the wiring diagram below for proper connection. All connections must be secure and comply with local electrical codes.

Figure 3: Detailed wiring diagram and technical specifications for the thermostat. Shows connections for House Ground, Neutral, Hot from Power Source, and To Heater.
3.3 Floor Sensor Installation
The 10Kohm floor sensor is included and essential for floor temperature control and protection. Install the sensor cable in a conduit or directly within the floor heating system, ensuring it is positioned centrally between heating elements for accurate readings. Do not cut or splice the sensor cable unless specifically instructed by the heating system manufacturer.

Figure 4: The included OJ Microline floor sensor, a black cable with a small probe at the end.
3.4 Montiranje termostata
- After wiring, carefully push the thermostat into the wall box.
- Secure the thermostat to the wall box using the provided screws.
- Pričvrstite prednju ploču.
- Vratite napajanje na prekidač.
4. Operacija
The OJ Microline UTN4-4999 is a non-programmable thermostat designed for simple and direct temperature control.
4.1 Podešavanje temperature
Za podešavanje željene temperature (zadane vrijednosti), koristite Up i Dole arrow buttons located below the display. The display will show the current temperature and the setpoint. The heating system will activate or deactivate to maintain the setpoint.

Figure 5: A hand interacting with the thermostat's buttons to adjust the temperature setting.
4.2 načina upravljanja
The thermostat offers three control modes, selectable based on your heating requirements and floor type:
- (A) Ambient temperature with Floor protection: The thermostat controls based on the room's air temperature, but will limit the floor temperature to prevent overheating, especially important for sensitive floor coverings like laminate or engineered wood.
- (B) Floor temperature with Floor protection: The thermostat controls directly based on the floor sensor reading, also with an upper limit for floor protection. This mode is ideal for maintaining a consistent floor surface temperature.
- (C) Ambient temperature without Floor protection: The thermostat controls solely based on the room's air temperature, without an upper limit on floor temperature. Use this mode only if your floor covering can withstand high temperatures.
Consult your heating system installer or the thermostat's advanced settings (if available, refer to the full technical manual for details) to select the appropriate control mode.
5. Održavanje
The OJ Microline UTN4-4999 thermostat is designed for minimal maintenance.
- čišćenje: Obrišite površinu termostata mekom,amp krpu. Ne koristite abrazivna sredstva za čišćenje, rastvarače ili hemijske sprejeve, jer mogu oštetiti ekran iliasing.
- GFCI test: Regularly test the built-in GFCI as per local electrical codes, typically monthly. Press the "TEST" button on the thermostat. The display should indicate a trip, and the heating will turn off. Press the "RESET" button to restore normal operation. If the GFCI does not trip or reset, contact a qualified electrician.
- inspekcija: Periodically inspect the thermostat and wiring for any signs of damage or loose connections. If any issues are found, disconnect power and consult a qualified electrician.
6. Otkrivanje problema
Ako imate problema s termostatom, pogledajte sljedeće uobičajene probleme i rješenja:
| Problem | Mogući uzrok | Rješenje |
|---|---|---|
| Displej termostata je prazan. | Nema napajanja termostata. | Check the circuit breaker. Ensure all wiring connections are secure. |
| Sistem grijanja se ne uključuje. | Setpoint is below ambient/floor temperature; GFCI tripped; wiring issue. | Increase setpoint. Check and reset GFCI. Verify wiring connections. |
| GFCI se često isključuje. | Ground fault in heating cable or wiring. | Immediately disconnect power and consult a qualified electrician to diagnose the ground fault. |
| Netačno očitavanje temperature. | Improper sensor placement; sensor damage; air drafts. | Ensure sensor is correctly placed. Inspect sensor for damage. Minimize drafts near the thermostat. |
Ako problem i dalje postoji nakon što ste pokušali pronaći ova rješenja, obratite se korisničkoj podršci ili kvalificiranom električaru.
7. Specifikacije
| Feature | Detalj |
|---|---|
| Broj modela | UDG-4999 |
| Brand | OJ Electronics |
| Tip kontrolera | Termostat |
| Stil | Nije moguće programirati |
| Voltage | 120V, 208V, 240V AC (Dual Voltage) |
| Maksimalno opterećenje | 15A (1800W @ 120V, 3600W @ 240V) |
| Frekvencija | 50/60 Hz |
| GFCI | Built-in Class A (5 mA trip level) |
| Senzori | Built-in Air Sensor, 10Kohm Floor Sensor (included) |
| Raspon ograničenja poda | +41 do +104°F (+5 do +40°C) |
| Raspon temperature okoline | +32 do +104°F (0 do +40°C) |
| Display Type | Digitalni sa pozadinskim osvetljenjem |
| Kontrolni metod | Kontrola tipkama (dodir) |
| Vrsta montaže | Zidni nosač |
| Usklađenost | c UL us Listed for USA and Canada |
| Dimenzije | 6 x 3.5 x 2.75 inča (pakovanje) |
| Težina artikla | 16 unci (1 funta) |

Figure 6: Key features of the thermostat including energy efficiency, simple operation, dual sensing, and built-in GFCI.
8. Informacije o garanciji
The OJ Microline UTN4-4999 Thermostat comes with a manufacturer's limited 3 godine garancijeOva garancija pokriva nedostatke u materijalu i izradi pri normalnoj upotrebi i servisiranju. Molimo sačuvajte dokaz o kupovini za potrebe reklamacije.
For detailed warranty terms and conditions, please refer to the documentation included with your product or visit the OJ Electronics official website.
9. Korisnička podrška
For technical assistance, troubleshooting beyond this manual, or warranty inquiries, please contact OJ Electronics customer support.
- Online podrška: Visit the official OJ Electronics webstranica za često postavljana pitanja, dodatne resurse i kontakt obrasce.
- Podrška putem e-pošte: Pogledajte pakovanje proizvoda ili službene webstranica za određene adrese e-pošte.
- Telefonska podrška: Pogledajte pakovanje proizvoda ili službene webstranica za brojeve telefona korisničke službe.
When contacting support, please have your product model number (UDG-4999) and purchase date available.