Functional Devices RIB01BDC

RIB01BDC Dry Contact Relay User Manual

Model: RIB01BDC

1. Uvod

This manual provides detailed instructions for the installation, operation, and maintenance of the Functional Devices RIB01BDC Dry Contact Relay. Please read this manual thoroughly before installation and operation to ensure safe and proper use of the device.

The RIB01BDC is an enclosed relay featuring a 20 Amp SPDT (Single Pole Double Throw) contact, a Class 2 dry contact input, and a 120 VAC power input. It is designed for various control applications where a dry contact input is used to switch a higher voltage or current load.

2. Sigurnosne informacije

WARNING: Risk of Electric Shock. Disconnect power before installation or servicing.

  • Instalaciju i servisiranje mora obavljati isključivo kvalificirano osoblje.
  • Osigurajte da se poštuju svi lokalni i nacionalni električni propisi.
  • Ne prekoračujte navedene električne nazivne vrijednosti uređaja.
  • Verify proper wiring connections before applying power.
  • The device is designed for indoor use in a NEMA 1 housing. Protect from moisture and extreme temperatures.

3. Značajke proizvoda

  • 20 Amp SPDT (Single Pole Double Throw) contact for versatile switching.
  • Class 2 dry contact input for control signal.
  • 120 VAC power input for relay coil.
  • NEMA 1 housing for general purpose indoor applications.
  • Integrated LED indicator for relay activation status.

4. Specifikacije

Tehničke specifikacije
ParametarVrijednost
Broj modelaRIB01BDC
Vrsta kontaktaSPDT (Jednopolni dvostruki bacač)
Current Rating20 Amps
Ulazna snaga Voltage120 Vac
Ulazna struja snage52mA @ 120Vac
Kontrolni ulazClass 2 Dry Contact
StanovanjeNEMA 1 Enclosed
Dimenzije proizvoda8 x 4 x 3 inča
Vrsta montažeScrew Mount
Kontakt materijalBakar

Ocene kontakata:

  • 20 A Resistive, 277 Vac
  • 20 A Ballast NO, 120/277 Vac
  • 10 A Ballast NC, 120/277 Vac
  • 10 A Tungsten NO, 120 Vac
  • 1 KS, 120 V AC
  • 2 KS, 277 V AC
  • 770VA Pilot Duty, 120Vac
  • 1110VA Pilot Duty, 277Vac

5. Instalacija i ožičenje

Refer to the product label and the diagram below for proper wiring connections. Ensure power is disconnected before beginning installation.

Functional Devices RIB01BDC Dry Contact Relay with wiring labels

Slika 1: Functional Devices RIB01BDC Dry Contact Relay showing the product label with wiring instructions and contact ratings. The relay is a gray enclosed unit with a red LED indicator and a conduit connection at the bottom from which colored wires emerge.

5.1. Montaža

The RIB01BDC relay is designed for screw mounting. Secure the device to a stable surface using appropriate fasteners through the mounting tabs on the enclosure.

5.2. Upute za ožičenje

The relay features pre-wired leads for power input, low-voltage dry contact input, and relay contacts. Follow the color codes carefully.

Power Input Wires (120 Vac):

  • CRNI: Connect to 120 Vac Line.
  • BIJELA: Connect to Neutral.

These wires supply power to the relay coil. The relay consumes approximately 52mA at 120Vac when activated.

Low-Voltage Dry-Contact Input Wires (Class 2 Wiring):

  • WHITE/BLUE: One side of the dry contact input.
  • WHITE/RED: Other side of the dry contact input.

These wires are for the control signal. When a dry contact closure is made across these two wires, the relay will activate.

Relay Contact Wires (SPDT):

  • YELLOW (COM): Common terminal for the relay contacts.
  • ORANGE (N/O): Normally Open contact. This contact closes when the relay is activated.
  • BLUE (N/C): Normally Closed contact. This contact opens when the relay is activated.

Connect your load to the appropriate relay contacts (COM and N/O for normally open operation, or COM and N/C for normally closed operation) based on your application requirements and the specified contact ratings.

6. Operacija

Once properly installed and wired, the RIB01BDC relay operates as follows:

  • When the 120 Vac power input is connected, the relay is ready for operation.
  • The relay activates when a dry contact closure is detected across the WHITE/BLUE and WHITE/RED input wires.
  • Upon activation, the integrated red LED indicator on the relay enclosure will illuminate.
  • When activated, the Normally Open (N/O) contact (Orange wire) will close to the Common (COM) contact (Yellow wire).
  • Simultaneously, the Normally Closed (N/C) contact (Blue wire) will open from the Common (COM) contact (Yellow wire).
  • When the dry contact input opens, the relay deactivates, the LED turns off, and the contacts return to their normal state (N/O opens, N/C closes).

7. Održavanje

The Functional Devices RIB01BDC Dry Contact Relay is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended:

  • Vizuelni pregled: Periodically inspect the relay and its wiring for any signs of damage, loose connections, or overheating.
  • čišćenje: Keep the enclosure clean and free of dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Uslovi okoline: Ensure the operating environment remains within specified temperature and humidity ranges to prevent premature failure.
  • Isključivanje struje: Always disconnect power to the relay before performing any inspection or maintenance.

8. Otkrivanje problema

If the RIB01BDC relay is not functioning as expected, consider the following common issues and solutions:

ProblemMogući uzrokRješenje
Relay does not activate (LED off)No 120 Vac power to relay coil.
Dry contact input not closed.
Neispravno ožičenje.
Verify 120 Vac supply to Black and White wires.
Check continuity of dry contact input (White/Blue and White/Red).
Review Section 5.2 for correct wiring.
Relay activates but load does not switchLoad not properly connected to relay contacts.
Load circuit open or faulty.
Load exceeds contact ratings.
Ensure load is connected to COM (Yellow) and N/O (Orange) or N/C (Blue) wires.
Test the load circuit independently.
Refer to Section 4 (Contact Ratings) to ensure load is within limits.
LED is on, but relay contacts are not switchingInternal relay failure.If all wiring and load checks are correct, the relay may be faulty and require replacement.
Rad sa prekidimaLabave veze ožičenja.
Unstable dry contact input.
Zategnite sve žičane veze.
Check the stability and reliability of the dry contact switch or sensor.

9. Garancija i podrška

For warranty information and technical support, please contact Functional Devices, Inc. directly. Refer to their official webnajnovije kontakt podatke potražite na web stranici ili na pakovanju proizvoda.

Note: Specific warranty terms and conditions may vary. Please retain your proof of purchase.

Povezani dokumenti - RIB01BDC

Preview Funkcionalni uređaji RIB releji: RITBTW2401B-BC i RITBTW2402B-BC mrežno kompatibilni releji - tehnički list
Tehničke specifikacije i dijagrami ožičenja za zatvorene BACnet MS/TP mrežne relejne uređaje Functional Devices RITBTW2401B-BC i RITBTW2402B-BC. Uključuje nazivne vrijednosti kontakata, ulaznu snagu, mrežne medije i konfiguracije DIP prekidača.
Preview Funkcionalni uređaji B3175 Mini Inverter serije: Uputstvo za instalaciju i upotrebu
Sveobuhvatni vodič za instalaciju i upotrebu za seriju mini invertera Functional Devices B3175, koji pokriva modele EMPS55125, EMPS110125, EMPS110250 i EMPS220250. Uključuje sigurnosne mjere, specifikacije, upute za montažu, ožičenje i održavanje.
Preview Upute za instalaciju i sigurnost ESRB-a i ESRN-a | Funkcionalni uređaji
Sveobuhvatni vodič za instalaciju, sigurnost, rad i rješavanje problema za module za upravljanje hitnom rasvjetom ESRB i ESRN kompanije Functional Devices. Uključuje dijagrame ožičenja, specifikacije i primjere primjene.amples.
Preview Functional Devices RIB24P-FA Fire Alarm Relay Datasheet and Terms of Sale
Detailed specifications, contact ratings, coil information, and comprehensive terms and conditions of sale for the Functional Devices RIB24P-FA enclosed 20 Amp DPDT fire alarm relay.
Preview ESRU1C Enclosed Relay: Specifications, Wiring, and Application Guide
Detailed guide for the Functional Devices ESRU1C enclosed relay, covering specifications, initial wiring verification, field inspection, and shunt relay application for emergency lighting systems.