ICM kontrole ICM402

ICM kontrole ICM402 Trofazni vod Voltage Uputstvo za upotrebu monitora

Model: ICM402

Uvod

The ICM Controls ICM402 is a robust three-phase line voltage monitor designed to provide critical protection for electrical systems. It continuously monitors for conditions such as phase loss, phase reversal, and voltage unbalance, ensuring the safe and reliable operation of connected equipment. This device is suitable for 50/60 Hz systems with a universal 3-phase input ranging from 190-600 VAC.

Ključne karakteristike

Specifikacije

Broj modelaICM402
Ulazni voltage190-600 VAC (3-Phase)
Control Voltage115, 208/240 VAC
Frekvencija50/60 Hz
Output Current (Y-OUT)30 Amps Max.
Dimenzije proizvoda4.5 x 4 x 2 inča
Težina6.56 unce
ProizvođačICM kontrole

Šta je u kutiji

The ICM402 package includes:

Sigurnosne informacije

UPOZORENJE: OPASNOST OD ŠOKA.
TURN OFF ALL POWER BEFORE SERVICING.
ALL TERMINALS MAY BE ENERGIZED.

Always ensure that power is disconnected at the source before attempting any installation, wiring, or maintenance on the ICM402 unit. Failure to do so can result in severe injury or death. This device should only be installed by qualified personnel in accordance with all local and national electrical codes.

ICM kontrole ICM402 Trofazni vod Voltage Monitor with terminal labels

Figure 1: ICM Controls ICM402 Unit Overview. Ova slika prikazuje vrh view of the ICM402 monitor, highlighting its various terminals and labels. Key markings include:

  • Y | Y-OUT (30 AMPS MAX.): Output terminal for the monitored circuit.
  • C | 115 VAC | 230 VAC: Control voltage ulazne terminale.
  • FAULT / ON LEDs: Indicators for operational status and fault conditions.
  • P/N ICM402 cRUus: Part number and safety certification.
  • L1, L2, L3 (190-600 VAC): Trofazni vod voltage ulazne terminale.
  • CUT WIRE FOR 50Hz: A red wire loop indicating a modification for 50Hz operation (if applicable).
  • NAPRAVLJENO U SAD: Country of manufacture.

The warning "SHOCK HAZARD: TURN OFF ALL POWER BEFORE SERVICING. ALL TERMINALS MAY BE ENERGIZED." is prominently displayed on the unit itself.

Instalacija i podešavanje

Proper installation is crucial for the correct operation and safety of the ICM402. Refer to Figure 1 for terminal identification.

  1. Isključivanje struje: Before beginning any wiring, ensure that all power to the circuit where the ICM402 will be installed is completely disconnected and locked out.
  2. Montaža: Mount the ICM402 in a suitable electrical enclosure, ensuring adequate ventilation and protection from environmental factors.
  3. Three-Phase Input Wiring (L1, L2, L3): Connect the three-phase line voltage (190-600 VAC) to the L1, L2, and L3 terminals. Ensure correct phase sequence for proper monitoring of phase reversal.
  4. Control Voltage Wiring (C, 115 VAC, 230 VAC): Connect the appropriate control voltage (115 VAC or 208/240 VAC) to the 'C' terminal and the corresponding voltage terminal (115 VAC or 230 VAC). This powers the internal circuitry of the monitor.
  5. Output Wiring (Y | Y-OUT): Connect the monitored circuit's control input or contactor coil to the Y and Y-OUT terminals. This output is rated for 30 Amps maksimum.
  6. Frequency Selection (50Hz/60Hz): The unit is factory set for 60Hz operation. If operating in a 50Hz system, locate the red wire loop labeled "CUT WIRE FOR 50Hz" and carefully cut it. Refer to Figure 1 for its location.
  7. Obnova napajanja: Once all wiring is securely connected and verified, restore power to the circuit.

Operacija

Upon power-up, the ICM402 will begin monitoring the three-phase line voltage. The status of the system is indicated by the two onboard LEDs:

The unit automatically resets once the fault condition is cleared and the voltage returns to normal operating parameters.

Održavanje

The ICM402 is designed for maintenance-free operation. However, periodic visual inspection is recommended to ensure:

Before any inspection or cleaning, always disconnect power to the unit.

Rješavanje problema

ProblemMogući uzrokRješenje
Unit not powering on (no LEDs)Bez kontrole voltage supply; Incorrect control voltage ožičenje.Provjerite kontrolnu jačinu zvukatage (115, 208/240 VAC) is present and correctly wired to C and appropriate VAC terminal. Check fuses/breakers.
FAULT LED is ON continuouslyPhase loss, phase reversal, or voltage unbalance detected.Check all three phases (L1, L2, L3) for presence and correct voltage. Verify phase sequence. Check for significant voltage unbalance between phases.
Unit cycles between ON and FAULTIntermittent power issue; Borderline voltage neravnoteža.Monitor incoming power for stability. Consult an electrician to diagnose power quality issues.
Output (Y | Y-OUT) not activatingFAULT condition present; Incorrect wiring to controlled device.Ensure no FAULT LED is illuminated. Verify wiring from Y/Y-OUT to the controlled device. Check the controlled device itself.

If troubleshooting steps do not resolve the issue, contact a qualified electrician or ICM Controls customer support.

Informacije o garanciji

ICM Controls products are manufactured to high standards and are typically backed by a manufacturer's warranty covering defects in materials and workmanship. For specific warranty terms, duration, and claim procedures, please refer to the warranty documentation included with your purchase or visit the official ICM Controls webSačuvajte dokaz o kupovini za slučaj reklamacije.

Korisnička podrška

For technical assistance, product inquiries, or support, please contact ICM Controls directly. Contact information can typically be found on their official website or on the product packaging. When contacting support, please have your product model number (ICM402) and any relevant purchase details ready.

Povezani dokumenti - ICM402

Preview ICM402 3-fazni monitor: Karakteristike, specifikacije i ožičenje
Detaljne informacije o ICM402 trofaznom monitoru, uključujući njegove karakteristike, tehničke specifikacije i dijagrame ožičenja. Ovaj uređaj štiti od gubitka faze, inverzije faze i fazne neravnoteže, idealan za kompresore.
Preview ICM401A trofazni monitor: Vodič za instalaciju zaštite od gubitka faze i inverzije faze
Detaljan vodič za instalaciju i specifikacije za ICM401A trofazni vod vol.tage monitor od ICM Controls. Saznajte više o njegovom radu, rješavanju problema i sigurnosnim mjerama opreza za zaštitu od gubitka faze i inverzije.
Preview ICM450A i ICM450A PLUS+ Programabilni trofazni linijski regulator jačine zvukatage Monitors - Installation, Operation & Application Guide
This guide provides detailed specifications, parameters, installation instructions, fault conditions, troubleshooting steps, and warranty information for the ICM450A and ICM450A PLUS+ programmable 3-phase line voltage monitors from ICM Controls.
Preview ICM450A i ICM450A PLUS+ Programabilni trofazni linijski regulator jačine zvukatagVodič za instalaciju i korištenje e-monitora
Ovaj vodič pruža detaljne informacije o instalaciji, radu i specifikacijama programabilnog trofaznog linijskog regulatora ICM450A i ICM450A PLUS+.tage monitore. Obuhvata funkcije kao što su zaštita od fazne neravnoteže, previsoka/premalona jačina zvukatagZaštita od električne energije, tajmer odgode prekida i Modbus komunikacija za PLUS+ model. Uključeni su i savjeti za rješavanje problema i ograničena jednogodišnja garancija.
Preview ICM493 Programabilni Single-Phase VoltagVodič za instalaciju e-monitora sa zaštitom od prenapona
Detaljan vodič za instalaciju, rad i primjenu ICM493 programabilnog jednofaznog Voltage Monitor sa zaštitom od prenapona. Obuhvata sigurnost, korake instalacije, kalibraciju, specifikacije i funkcije dugmadi za HVAC i industrijske primjene.
Preview Sentry 3N1: Jednofazni VoltagVodič za instalaciju prekidača sa zaštitom od prenapona i električne energije | ICM Controls
Sveobuhvatni vodič za instalaciju, rad i rješavanje problema za ICM Controls Sentry 3N1, jednofazni vol...tagIsključivanje zaštićeno od prenapona i električne prenaponske zaštite s ICM492D voltage monitor i prenaponska zaštita ICM517A.