Intermatic T174

Intermatic T174 DPST 24 Hour Time Switch Instruction Manual

Model: T174

Uvod

This manual provides instructions for the installation, operation, and maintenance of the Intermatic T174 DPST 24 Hour Time Switch. This electromechanical timer is designed for controlling electrical loads over a 24-hour period.

Intermatic T174 DPST 24 Hour Time Switch with Type 1 Indoor Enclosure

Image: Intermatic T174 DPST 24 Hour Time Switch. This image shows the front view of the timer with its gray metal enclosure and the dial for setting time.

Sigurnosne informacije

WARNING: Risk of electric shock. Installation and servicing must be performed by qualified personnel only. Disconnect power at the circuit breaker or fuse box before installing or servicing the timer.

  • Uvijek se pridržavajte lokalnih električnih propisa i propisa.
  • Provjerite da li napajanje odgovara jačini zvuka tajmera.tage rating (208-277V AC).
  • Do not exceed the maximum current and horsepower ratings of the timer.
  • This device is intended for indoor use in a Type 1 enclosure.

Sadržaj paketa

The Intermatic T174 Time Switch package typically includes:

  • One (1) Intermatic T174 Time Switch Unit
  • Uputstvo za upotrebu
  • Two (2) Trippers for setting ON/OFF times

Postavljanje i instalacija

The Intermatic T174 is designed for fixed installation. Proper wiring is crucial for safe and correct operation.

Montaža

  1. Choose a suitable indoor location for mounting the timer, ensuring it is protected from moisture and extreme temperatures.
  2. Securely mount the timer's enclosure to a wall or suitable surface using appropriate fasteners.

Wiring (DPST Configuration)

The T174 features a Double Pole, Single Throw (DPST) contact form, meaning it controls two independent circuits or a single 2-pole circuit simultaneously.

  1. DISCONNECT ALL POWER to the circuit at the main service panel before proceeding.
  2. Otvorite kućište tajmera.
  3. Connect the incoming power lines (L1 and L2 for 208-277V AC) to the designated "LINE" terminals on the timer.
  4. Connect the load wires (to the device being controlled) to the designated "LOAD" terminals. Ensure correct polarity if applicable.
  5. Uvjerite se da su sve žičane veze čvrste i sigurne.
  6. Close the timer's enclosure securely.
  7. Vratite napajanje u kolo.

Ako niste sigurni u vezi s bilo kojim postupkom ožičenja, obratite se kvalificiranom električaru.

Uputstvo za upotrebu

The T174 uses a mechanical dial and trippers to set the ON/OFF schedule.

Postavljanje trenutnog vremena

  1. Rotate the timer dial clockwise until the current time aligns with the "TIME SET" arrow or indicator on the timer mechanism.
  2. Ensure AM/PM is correctly observed if the dial has such markings.

Setting ON/OFF Times

The timer comes with two trippers: one "ON" tripper and one "OFF" tripper. Additional trippers can be purchased separately (Extra Trippers 11Z965).

  1. Locate the "ON" tripper (typically silver or light-colored) and the "OFF" tripper (typically black or dark-colored).
  2. Snap the "ON" tripper onto the dial at the desired time you want the connected device to turn ON.
  3. Snap the "OFF" tripper onto the dial at the desired time you want the connected device to turn OFF.
  4. You can set up to 12 ON/OFF cycles per 24-hour period using additional trippers. The minimum time setting is 1 hour.

Manual Override

The T174 typically includes a manual override switch or lever. This allows you to temporarily turn the connected device ON or OFF without affecting the programmed schedule. Refer to the specific markings on your timer for the manual override function.

Day Skipper Function

The timer features a Day Skipper function, allowing you to prevent operation on specific days of the week. Consult the detailed instruction guide included with your unit for specific setup of this feature.

Održavanje

The Intermatic T174 Time Switch is designed for reliable, long-term operation with minimal maintenance.

  • Periodically inspect the timer for any signs of damage or loose connections.
  • Keep the enclosure clean and free from dust and debris.
  • Do not attempt to lubricate internal components.

Rješavanje problema

Problem Mogući uzrok Rješenje
Tajmer ne radi. Nema napajanja za tajmer. Check circuit breaker or fuse. Ensure wiring connections are secure.
Connected device does not turn ON/OFF at programmed times. Incorrect tripper placement or current time setting. Verify tripper positions and ensure the current time is accurately set on the dial. Check manual override switch position.
Timer motor is noisy. Normal operation for some mechanical timers. If noise is excessive or new, contact support.
Timer operates but device does not. Faulty wiring to the load or issue with the connected device. Verify load wiring. Test the connected device directly to ensure it is functional.

Specifikacije

Feature Detalj
Broj modela T174
Tip Elektromehanički tajmer
Operacija 24 sata
Broj polovica 2
Kontakt obrazac DPST-NO (Double Pole, Single Throw - Normally Open)
Voltage 208-277V AC
AmpDob 40 A
Contact HP @ 120V 2 hp
Contact HP @ 240V 5 hp
Day Skipper Da
Enclosure Type Steel, Type 1 Indoor Enclosure
Završi Siva emajl
Minimum Time Setting 1 sat
Postavka maksimalnog vremena 23 sati
Maximum ON/OFF Cycles 12
Dimenzije (V x Š x D) 7 13/16 in x 5 in x 3 in (Approximate)
Težina artikla 2.75 - 2.8 Pounds
Included Trippers 2
UPC 078275174214
Proizvođač Intermatic Incorporated

Garancija i podrška

The Intermatic T174 Time Switch comes with a manufacturer's warranty. For specific warranty details, please refer to the documentation included with your product or visit the official Intermatic website.

For technical support, troubleshooting assistance, or to inquire about replacement parts, please contact Intermatic customer service. You can often find support information and additional resources on the Intermatic prodavnica na Amazonu ili njihov službeni korporativni website.

Povezani dokumenti - T174

Preview Intermatic T105 24-satni vremenski prekidač: Vodič za instalaciju, ožičenje i upotrebu
Sveobuhvatni vodič za Intermatic T105 mehanički vremenski prekidač sa 24-satnim brojčanikom. Obuhvata specifikacije modela, sigurnosna upozorenja, upute za ožičenje za različite konfiguracije (SPNO, SPNC, SPDT), postupke programiranja i ručni rad. Uključuje detaljnu tabelu električnih karakteristika i preporuka za presjek žica.
Preview Intermatic T103 24-satni vremenski prekidač: Uputstvo za instalaciju i upotrebu
Detaljan vodič za Intermatic T103 24-satni vremenski prekidač, koji obuhvata specifikacije, sigurnosna upozorenja, upute za ožičenje, programiranje i rad. Pogodan za unutrašnju upotrebu sa napajanjem 120/208/240 VAC.
Preview Intermatic elektromehanički vremenski prekidači serije T170, T1400 i T1800
Sveobuhvatni detalji o Intermatic T170, T1400 i T1800 seriji 24-satnih elektromehaničkih vremenskih prekidača, koji obuhvataju karakteristike, specifikacije, nazivne vrijednosti, varijacije modela i dijagrame ožičenja za komercijalne, industrijske i stambene primjene.
Preview Intermatic T104 24-satni vremenski prekidač - Specifikacije i upute
Sveobuhvatni vodič za Intermatic T104 vremenski prekidač sa 24-satnim brojčanikom, koji detaljno opisuje njegove specifikacije, električne nazivne vrijednosti, sigurnosna upozorenja, upute za ožičenje, postupke programiranja i smjernice za upotrebu. Uključuje tehničke podatke i savjete za rješavanje problema.
Preview Intermatic EJ351 Zidni prekidač za unutrašnju upotrebu: Vodič za instalaciju, programiranje i rješavanje problema
Sveobuhvatni vodič za instalaciju, programiranje i rješavanje problema s Intermatic EJ351 unutarnjim zidnim tajmerom. Naučite kako postaviti rasporede, koristiti automatski i ručni način rada i riješiti uobičajene probleme.
Preview Intermatic Spring Wound Interval Timer Installation and Operation Guide
Detailed installation, operation, and application guide for Intermatic spring wound interval timers (FF and FD models). Includes switch ratings, wiring diagrams, and warranty information.