1. Uvod
The GEYA G2R-63 Automatic Transfer Switch (ATS) is a PC class infrequent change-over switch designed for AC systems with AC 50-60Hz and rated current 6A-63A. It features a two-station design, typically used for a common power supply (A) and a backup power supply (B). Its primary function is to automatically switch to the backup power supply when the main power fails, ensuring uninterrupted power to the load. The switching speed is less than 50 milliseconds.
When both power sources A and B are available, the device prioritizes the common power supply (A).
2. Tehničke specifikacije
Refer to the table below for detailed technical specifications of the GEYA G2R ATS.

Image: Detailed technical specifications including current ratings, voltage, frequency, and protection ranges.
| Atribut | Vrijednost |
|---|---|
| Nazivna radna struja Ie (A) | 06A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Nazivna izolacija Voltage Ui | 690V |
| Nazivna otpornost na impuls Voltage Uimp | 8kV |
| Nazivno radno izdanjetage Ue | AC220V/AC110V |
| Nazivna frekvencija | 50/60Hz |
| Klasa | PC klasa: može se uključiti i opteretiti bez stvaranja struje kratkog spoja |
| Pole Number | 2P, 4P |
| Nazivna struja kratkog spoja Iq | 5kA |
| Uređaj za zaštitu od kratkog spoja (osigurač) | RT16-00-63A |
| Kontrolni krug | Nazivna kontrola voltage Us AC220V/110V, 50/60Hz. Normal working conditions 85%Us-110%Us |
| Pomoćni krug | AC220V/110V 50/60Hz Ie=5A |
| 220V Overvoltage/Undervoltage Zaštitni raspon | Undervoltage: 175V (Recovery: 195V), Overvoltage: 260V (Recovery: 240V ±5V) |
| 110V Overvoltage/Undervoltage Zaštitni raspon | Undervoltage: 85V (Recovery: 95V), Overvoltage: 145V (Recovery: 130V ±5V) |
| Mehanički život | ≥8000 puta |
| Electrical Life | ≥1500 puta |
| Kategorija upotrebe | AC-31B |
| Certifikacija | CE, CB |
Dimenzije

Image: Detailed dimensions for 2P and 4P models, screw torque, and terminal width.
- 2P Model Dimensions: 108 mm (Dužina) x 50.5 mm (Širina) x 78 mm (Visina)
- 4P Model Dimensions: 108 mm (Dužina) x 82.5 mm (Širina) x 78 mm (Visina)
- Moment zavrtnja: 2.5Nm
- Terminal Width: 7.4mm
3. Sigurnosne informacije
Always observe the following safety precautions when installing, operating, or maintaining the GEYA G2R ATS:
- Instalaciju i održavanje treba obavljati samo kvalificirano osoblje.
- Ensure all power sources are disconnected before performing any wiring or maintenance.
- Verify correct phase sequence for input power supply as indicated in the wiring instructions.
- Ne koristite uređaj ako izgleda oštećeno ili neispravno.
- Izbjegavajte dodirivanje električnih komponenti pod naponom.
- Osigurajte pravilno uzemljenje u skladu s lokalnim električnim propisima.
4. Proizvod je gotovview
The GEYA G2R ATS is designed for seamless power transfer between a common power supply and a backup power supply. Key features include:
- Automatic and Manual operation modes.
- Overvoltage i Undervoltage zaštita.
- Indicator lights for power status and abnormal conditions.
- Din Rail mounting for easy installation.
Komponente i indikatori

Slika: Front view of the 2P model G2R-63II ATS, showing input terminals (I, II, N1 A1, N2 A2), Manual/Auto switch, Load ON indicator, and Load output terminals (LOAD N A).

Slika: Front view of the 4P model G2R-63II ATS, showing input terminals (I, II, N1 A1, B1 C1, Generator, Normal Power), Manual/Auto switch, Load ON indicator, and Load output terminals (LOAD N A B C).
- (I) N1 A1 / B1 C1: Common Power Supply Input (Live)
- (II) N2 A2 / B2 C2: Backup Power Supply Input (Live)
- LOAD N A / B C: Load Output Terminals
- Ručni/Automatski prekidač: Selects operation mode.
- Indikator uključenog opterećenja: Green light indicates load is powered.
- Power Indicator Lights (Red/Green): Indicate status of power sources.
- Manual Operation Handle: Za ručno prebacivanje.
- Din-Rail Buckle: For mounting on a DIN rail.
5. Instalacija i ožičenje
The GEYA G2R ATS is designed for Din Rail mounting. Ensure the mounting surface is stable and secure.
Upute za ožičenje
VAŽNO: All wiring must be performed by a qualified electrician and with all power sources disconnected.

Image: Detailed wiring diagram showing connections for common power supply, backup power supply, and load, along with indicator light explanations.

Image: Wiring diagram for a 2P (single-phase) G2R-63II ATS, illustrating connections for backup and common power supplies to a load, along with voltage postavke zaštite.

Image: Wiring diagram for a 4P (three-phase) G2R-63II ATS, illustrating connections for backup and common power supplies to a load.
- Povežite Common Power Supply (I) live wire to terminal N1 A1 (or B1 C1 for 4P) and neutral wire to N2 A2 (or B2 C2 for 4P).
- Povežite Backup Power Supply (II) live wire to terminal N1 A1 (or B1 C1 for 4P) and neutral wire to N2 A2 (or B2 C2 for 4P).
- Povežite Load Output live wire to terminal LOAD N A (or B C for 4P) and neutral wire to LOAD N A.
- Ensure the input power supply is connected in the correct phase sequence.
- Secure all connections with a screw torque of 2.5Nm.
Note: The input power supply must be connected in the correct phase sequence.
6. Uputstvo za upotrebu
The GEYA G2R ATS supports both manual and automatic operation modes.
6.1. Ručni način rada
In manual mode, you can manually switch between the two power sources using the selector switch.
- Ensure both power sources are turned on.
- Set the selector switch to "Manual".
- Manually toggle the switch to select either power source (I) or (II) to supply power to the load.
Important Note on Manual Operation:
- Manual operation allows for electrical switching, but the speed of operation by users can vary.
- Excessive silver alloy loss is possible during manual operation if not performed carefully.
- The selector switch should only be moved to the manual position after all power has been cut off, typically for inspection and maintenance.
6.2. Automatski način rada
In automatic mode, the ATS will automatically detect power failures and restore power, switching between the main and backup supplies.
- Set the selector switch to "Auto".
- When the main power supply (I) is disconnected, the product will automatically switch to the backup power supply (II).
- When the main power supply (I) is restored, the product will automatically switch back to the main power supply.
Important Note on Automatic Mode:
- The control circuit is immediately energized when the selector switch is in the electric (Auto) position.
- The internal switch is designed to handle the changeover. The coil can operate normally within 85%-110% of the rated operating voltage.
- Preniska ulazna voltage may cause the coil to overheat and burn out.
6.3. Overvoltage i Undervoltage Zaštita
The G2R ATS includes built-in voltage protection features:
- If the main power supply voltage pada ispod undervoltage threshold (e.g., 175V for 220V systems), the ATS will automatically switch to the backup power supply.
- If the main power supply voltage se uzdiže iznad overvoltage threshold (e.g., 260V for 220V systems), the ATS will automatically switch to the backup power supply.
- Nakon što je voltage returns to normal range (e.g., above 195V for undervoltage recovery, below 240V for overvoltage recovery), the ATS will switch back to the main power supply.
Napomena:
When abnormal voltage returns to normal voltage, the indicator light flashes for 15 seconds (with a delay of 15 seconds) and then returns to normal light. The power supply of this circuit will only be considered normal in the chip judgment after 15 seconds. Switch between primary and backup logic again.
6.4. Video demonstracije proizvoda
Video: Demonstration of manual and automatic switching, and overvoltage/undervoltage protection functionality of the GEYA G2R ATS.
7. Održavanje
Regular maintenance helps ensure the longevity and reliable operation of your GEYA G2R ATS.
- Povremeno provjeravajte sve spojeve ožičenja kako biste se uvjerili da su čvrsti i bez korozije.
- Check the device for any signs of physical damage, overheating, or unusual odors.
- Održavajte uređaj čistim i bez prašine i ostataka.
- If the device is in manual mode for an extended period, ensure the selector switch is returned to "Auto" for automatic protection.
- For any internal inspection or repair, always disconnect all power sources and consult a qualified electrician.
8. Otkrivanje problema
If you encounter issues with your GEYA G2R ATS, refer to the following common troubleshooting steps:
| Problem | Mogući uzrok | Rješenje |
|---|---|---|
| Load not receiving power in Auto mode. | Both main and backup power supplies are off, or one is outside voltage pragovi. | Check both power sources. Ensure voltages are within normal operating range. Verify indicator lights. |
| Indicator light flashing for Common/Backup power supply. | Abnormal voltage (ispod ili preko voltage) detected on that power supply. | Provjerite voltage of the indicated power supply. The ATS will switch to the other source if available. It will return to normal after 15 seconds if voltage stabilizuje. |
| Device not switching automatically. | Selector switch is in "Manual" mode. | Switch the selector to "Auto" mode. |
| Device feels hot or smells burnt. | Control coil overheating due to low input voltage or internal fault. | Immediately disconnect all power. Do not operate. Contact a qualified electrician for inspection and repair. |
9. Savjeti za korisnike
- Solar Power Integration: Yes, this ATS can be used with solar power systems. Connect your inverter output (from solar panels, MPPT, and batteries) to one of the power inputs (e.g., as the backup power source). Ensure the inverter is a pure sine wave type and has a power output above 2000W for optimal performance.
- Određivanje prioriteta: Remember that when both power sources are available, the ATS is designed to prioritize the common power supply (Source A).