GEYA GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
GEYA GRD9L-R Automatic Reclosing RCD Leakage Circuit Breaker User Manual
Model: GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
1. Uvod
This manual provides essential information for the safe and effective installation, operation, and maintenance of the GEYA GRD9L-R Automatic Reclosing RCD Leakage Circuit Breaker. This device is designed to enhance electrical safety by automatically reclosing when a Residual Current Device (RCD) trips unexpectedly, reducing manual intervention and improving system efficiency. It is suitable for various applications including meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.
Molimo vas da pažljivo pročitate ovaj priručnik prije instalacije i upotrebe i sačuvate ga za buduću upotrebu.
2. Ključne karakteristike
- Automatsko ponovno zatvaranje: Coupled with a leakage protection circuit breaker (RCD), it automatically recloses when the RCD trips unexpectedly. This eliminates the need for manual reclosing, reduces maintenance costs, and promptly corrects errors to improve efficiency.
- Integrated Reclosing Attempts: Features 3 integrated reclosing attempts. If continuous reclosing occurs within 15 minutes, an alarm can be sent via an auxiliary contact.
- Manual/Automatic Selector: Equipped with a manual/automatic selector switch for flexible operation.
- Dual Locking Mechanism: Incorporates a double mechanical/electronic locking system for enhanced safety.
- Kompatibilnost dodatne opreme: Can be adapted with auxiliary contacts, alarm contacts, shunt releases, and undervoltage izdanja.
- Reclosing Time Reset: Reclosing attempt counts are reset if no trip occurs or if a manual reset is performed within 15 minutes of a successful reclosure.
3. Tehničke specifikacije
| Specifikacija | Vrijednost |
|---|---|
| Broj modela | GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA |
| Brand | GEYA |
| Voltage | 220 Volts |
| Current Rating | 63 A (Nominal Current) / 30 mA (Residual Current Sensitivity) |
| Tip prekidača | RCD (uređaj rezidualne struje) |
| Broj polovica | 2 |
| Vrsta montaže | Wall Mount, Flush Mount |
| Dimenzije paketa | 12 x 11.6 x 9.1 cm |
| Težina | 350 grama |
4. Postavljanje i instalacija
Installation of the GEYA GRD9L-R device should only be performed by a qualified electrician in accordance with local electrical codes and regulations. Ensure the main power supply is disconnected before commencing any installation work.
4.1 Montaža
The device supports both wall mount and flush mount installations. It is designed to be installed on a DIN rail alongside an RCCB and auxiliary components.

Slika 4.1: The GRD9L-R device shown installed on a DIN rail with an auxiliary contact module and an RCCB (Residual Current Circuit Breaker). Arrows indicate the direction of installation onto the rail.
Koraci instalacije:
- Mount the RCCB onto the DIN rail.
- Mount the GRD9L-R automatic reclosing device next to the RCCB.
- If required, mount the auxiliary contact module next to the GRD9L-R.
- Ensure all components are securely fastened to the DIN rail.
4.2 Ožičenje
Connect the GRD9L-R device according to the provided wiring diagram. Ensure correct polarity and secure terminal connections. The device is designed to be coupled with an RCCB for leakage protection.

Slika 4.2: Example application wiring diagram. This diagram illustrates how the GRD9L-R (labeled RD) integrates with an alarm lamp, an RCCB, and multiple Miniature Circuit Breakers (MCBs) protecting various loads. Red lines represent live connections, and blue lines represent neutral connections.
Važno: Verify all connections before restoring power. Incorrect wiring can lead to malfunction or electrical hazards.
5. Uputstvo za upotrebu
5.1 Manual/Automatic Selector
The GRD9L-R device features a selector switch for choosing between manual and automatic operation modes.
- AUTO način rada: In this mode, the device will automatically attempt to reclose the coupled RCCB after a trip, following the programmed reclosing logic.
- MANU Mode: In this mode, the automatic reclosing function is disabled. The RCCB must be manually reclosed after a trip.

Slika 5.1: The GEYA GRD9L-R device with its AUTO/MANU selector switch clearly visible. The diagram illustrates the automatic reclosing logic, showing the sequence of ON/OFF states and delay times for the 1st, 2nd, and 3rd trip attempts. It also indicates the PWR (Power) and AUX (Auxiliary) connections.
5.2 Automatic Reclosing Logic
The device attempts to reclose the RCCB up to three times after an unexpected trip. The reclosing intervals are fixed.

Slika 5.2: Detailed functions diagram for the GRD9L-R. This diagram shows the LED indicators (PWR), trip times (1, 2, 3, 4), and the state of the MCB/RCCB (Auto) over time. It illustrates the reclosing logic with specific delay times (10s, 15min, 60s, 300s) between attempts. The note indicates that if the interval between two closings exceeds 15 minutes, the program clears accumulated closing times. Fixed closing time intervals are 10s, 60s, and 300s.
- First Trip: After the RCCB trips, the device waits for 10 seconds, then attempts to reclose.
- Second Trip: If the RCCB trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts to reclose.
- Third Trip: If the RCCB trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts to reclose.
- Zaključavanje: If the RCCB trips a fourth time, or if reclosure is unsuccessful after the third attempt, the device enters a locked-out state (LOCK) and requires manual intervention.
- Resetting Attempts: If the interval between two consecutive trips exceeds 15 minutes, the reclosing attempt counter is reset. The counter also resets after a successful reclosure if no further trips occur within 15 minutes, or upon manual reset.
The fixed reclosing time intervals are 10 seconds, 60 seconds, and 300 seconds. For customization of closing times or intervals, please contact GEYA customer support.
5.3 Funkcija zaključavanja
The device includes a locking mechanism for safety during maintenance or inspection. When the lock function is activated, the RCCB cannot be closed, preventing accidental power restoration.

Slika 5.3: The GRD9L-R device demonstrating the locking function. A padlock is inserted into the designated lock slot, preventing the switch from being moved to the ON position. A note indicates that the RCCB cannot close when the lock function is activated, and the padlock diameter should be less than 3.5 mm.
To activate the locking function, insert a padlock with a shackle diameter less than 3.5 mm into the designated slot on the device. This ensures that the RCCB remains open during circuit checks or maintenance, enhancing safety.
6. Održavanje
The GEYA GRD9L-R device is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.
- Vizuelni pregled: Regularly inspect the device for any signs of physical damage, loose connections, or overheating.
- Test funkcije: Periodically test the RCCB's trip function using its test button. Ensure the GRD9L-R responds by attempting to reclose.
- čišćenje: Uređaj održavajte čistim i bez prašine i ostataka. Za čišćenje koristite suhu, meku krpu. Ne koristite tekuća sredstva za čišćenje.
- Profesionalna provjera: It is recommended to have the electrical system, including the GRD9L-R, inspected by a qualified electrician at least once a year.
Uvijek isključite napajanje prije bilo kakvog održavanja ili pregleda.
7. Otkrivanje problema
This section provides guidance for common issues. For problems not listed here or if issues persist, contact GEYA customer support.
| Problem | Mogući uzrok | Rješenje |
|---|---|---|
| Device does not reclose after RCCB trip. |
|
|
| Alarm contact activated frequently. |
|
|
| RCCB cannot be closed when lock function is active. | Padlock is inserted, activating the safety lock. | Remove the padlock from the locking slot. |
8. Sigurnosne informacije
- Električna opasnost: Ovaj uređaj radi s visokom jačinom zvukatage. Installation, maintenance, and troubleshooting must only be performed by qualified and authorized personnel.
- Isključite napajanje: Always ensure the main power supply is completely disconnected and locked out before working on the device or associated circuitry.
- Pravilno uzemljenje: Ensure all electrical installations are properly grounded according to national and local electrical codes.
- Uslovi okoline: Ne izlažite uređaj vlazi, ekstremnim temperaturama ili korozivnim okruženjima.
- Namjena: Use the device only for its intended purpose as an automatic reclosing mechanism for RCDs. Do not modify the device.
9. Garancija i podrška
GEYA products are manufactured to high-quality standards. For warranty information, please refer to the documentation provided with your purchase or contact your local GEYA distributor. For technical support, inquiries about customization, or service, please visit the official GEYA websajtu ili kontaktirajte korisničku podršku.
Proizvođač: ZHEJIANG GEYA ELECTRICAL CO.,LTD
Povezani dokumenti - GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
![]() |
GEYA katalog električne opreme - Prekidači, kontaktori i još mnogo toga Sveobuhvatan katalog GEYA električnih proizvoda, uključujući minijaturne prekidače, kontaktore, prekidače za prenos i drugu sigurnosnu opremu, s detaljnim specifikacijama, primjenama i standardima usklađenosti. |
![]() |
GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide Comprehensive instruction manual and technical guide for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications, features, technical specifications, installation, networking, troubleshooting, and dimension details for intelligent electrical systems. |
![]() |
GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide Detailed instruction manual for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications in intelligent household electricity management and photovoltaic systems, function features, technical parameters, panel and wiring diagrams, installation, networking setup with Tuya Smart app, common faults, and dimensions. Essential guide for safe and efficient electrical control. |
![]() |
GEYA Miniature Circuit Breakers, Contactors, and Transfer Switches Catalog | Technical Specifications Comprehensive catalog from GEYA detailing Miniature Circuit Breakers (MCB), Residual Current Circuit Breakers (RCCB), Residual Current Circuit Breakers with Overcurrent Protection (RCBO), Molded Case Circuit Breakers (MCCB), AC Contactors, Automatic Transfer Switches, and Intelligent Circuit Breakers. Includes technical specifications, scope of application, product features, and compliance information for various models, serving industrial, commercial, and residential applications. |
![]() |
GEYA Low Voltage Electrical Products Catalog | Industrial Control Integration Comprehensive catalog of GEYA low voltage electrical appliances and automation control products, including circuit breakers, relays, contactors, timers, and more. Featuring industrial control integration solutions. |
![]() |
GEYA WiFi serija inteligentnih minijaturnih prekidača - Upute za upotrebu Detaljna uputstva za upotrebu i često postavljana pitanja za GEYA WiFi seriju inteligentnih minijaturnih prekidača (serija ZJSB9). Saznajte više o instalaciji, podešavanju, rješavanju problema, sigurnosti i primjeni za električnu zaštitu pametnog doma. |
Ask a question about this manual
Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.